air conditioning

Air conditioning system heating and cooling the air inlet of the room with cascade control

The cascade controller is used for the absolute pressure of a VAV

In recent years, variable volume air (VAV) systems have been widely used in air conditioning.

Systems can save energy while maintaining indoor comfort with variable frequency (VFD) drive technology

And building automation systems (BAS). Different from fixed air Volumetric systems in which the temperature of the supplied air is regulated due to the constant air flow to optimize control and energy consumption

VAV systems can regulate air temperature and air flow.

This control system has variable speed fans, mixing dampers, hot water heating coil and cold water cooling coil.

The most important functions are:

  • Temperature control with (minimum and maximum limit)
  • Fan pressure control
  • Room air quality control

Functional diagrams / sequence diagrams

Cascading temperature control

TSu

SpTSuMax

PrSpLoTSu

PrSpHiTSu

SpTSuMin

PrSpLoT

PrSpHiT

TR

Inlet air temperature

Maximum inlet air temperature set point

Inlet air current temperature lower setting point

High setting point of the inlet air current temperature

Inlet air temperature setting point

Low current temperature setting point

High current setting point

room temperature

Inlet air temperature control

Vlv-Pos

DmpMx’Pos

Actg=1

Actg=0

Hcl’Vlv’Pos

Ccl’Vlv’Pos

PrSpLoTSu

PrSpHiTSu

Valve position

Position of the mixed air damper

Damper control to heat the mixed air

Damper control to heat the mixed air

Heating valve position

Heating valve position

Inlet air current temperature lower setting point

High setting point of the inlet air current temperature

Seasonal temperature compensation

SpTR

PrSpHiT

PrSpShftHi

PrSpLoT

PrSpShftLo

TOa

Room temperature setting

High current setting point

Change the current top point

Low current temperature setting point

Change the current low point

Outdoor air temperature

Pressure control

Fan’Spd

SpP

P

Fan speed

Pressure adjustment point

Pressure

Air quality control

DmpMx’PosOa

DmpMx’PosOaMin

AQualR

SpAQualR

Position of air mixer dampers for outside air

Minimum position of air mixer dampers for outside air

Room air quality

Room air quality adjustment point

Description of functions

1- Waterfall temperature control (room / inlet air)

The adjustment point above and below calculates the inlet air at the outside temperature.

See the cascade control chart on the pages above

2- Basic settings for temperature control

Adjustment points for high and low room temperature

See Seasonal Temperature Compensation Performance Chart

3- Seasonal temperature compensation

The up and down adjustment point adjusts the room temperature based on the outside temperature

See Seasonal Temperature Compensation Performance Chart

4- Basic air quality settings

Settings for air quality

See Performance chart, basic air quality control settings.

5- Current operation mode

Current mode performance report: Off | Bright

6- The reason for the current situation

Report the reason for the current situation:

Exception | Function mode switch | Manual work mode | Scheduling | Performance change operation

7- Select the manual operation mode

Function status to: Automatic | Turns off or on

8- Cooling at night (free cooling)

If the conditions for cooling the room air outside the operating mode are on, it turns on the fans.

9- Common error (error indicators)

Display error in HMI or display pages

Leave a Reply

Your email address will not be published. Required fields are marked *